| Permit Intake | Withdrawn | As the proposed value of work exceeds 50% of the Assessor's assessed value of the structure, the proposed work constitutes a substantial improvement for the purposes of Chapter 78 of the City Code. Please do one of the following: a) provide a Benchmark Certificate or Elevation Certificate to verify that the structure meets the required Advisory Base Flood Elevation; b) submit an appraisal to confirm that the proposed work does not exceed 50% of the value of the existing structure; or c) elevate the entire structure to meet the required elevation or d) submit a letter from: Louisiana Office of Historic Preservation, Capitol Annex Building, 1051 North Third Street, Baton Rouge, Louisiana 70802. Phone: (225) 342-8160 The valuation of work of all open permits is used.
|
| Permit Intake | Resolved | A Benchmark Certificate is required for this permit application. The Benchmark Certificate must bear the live seal of a Louisiana registered land surveyor and dated within the last six (6) months. This must be on the Safety & Permits three-part form dated September 30, 2016. |
| Permit Intake | Resolved | Please provide the Name and State License number of the General Contractor or the Homeowner Affidavit for Exemption from Licensure. The affidavit for exemption from licensure is not allowed for properties that are under ownership of an LLC or INC. If work to be performed is on a residential structure, make sure the State License # authorizes you to perform residential work. If work to be performed is on a commercial structure, make sure your State License # authorizes you to perform commercial work. |
| Permit Intake | Resolved | Please submit a detailed and signed contract/detailed estimate for the work to be performed, including labor. |
| Permit Intake | Resolved | Please secure a demolition permit. |
| Plan Review | Resolved | Approved smoke detectors should be provided in each bedroom and outside of each bedroom as required by Sec. R314 IRC 2012 ed. Please provide outside each bedroom. |
| Plan Review | Resolved | Approved carbon monoxide detectors should be provided outside each separate sleeping area for any dwelling with an attached garage or fuel-fired appliances as per Section R315 of the IRC 2012 ed. |
| Plan Review | Resolved | All sleeping areas shall have at least one operable emergency escape and rescue opening as per Section R310.1 of the IRC 2012 ed. |
| Plan Review | Resolved | 2x8 ceiling joists above the kitchen and bedroom #2 appear to be overspanned. Please revise or indicate supporting structure. |
| Plan Review | Resolved | Guards are required along open-sided walking surfaces, including stairs, ramps, and landings, that are located more than 30 inches above grade as per Sec. R312.1 IRC 2012 ed. Please provide around the front porch. |
| Plan Review | Resolved | Provide attic ventilation as required by Sec. R806 of the IRC 2012 ed. Overhangs within 3ft of the property line should not be vented. |
| Plan Review | Resolved | Provide attic access in compliance with Sec. R807 IRC 2012 ed. |
| Plan Review | Resolved | This project has been reviewed by Erin Guerra. For email correspondence, please send to emguerra@nola.gov.
Note: Please make sure to email the reviewer if you upload any documents on OneStop.
|
| Zoning | Resolved | Table 13-2 requires side yard setbacks of 10% of the lot width or 3 feet, whichever is GREATER. Please revise or seek a waiver from the Board of Zoning Adjustments. |