Type: Renovation (Non-Structural)
Location: 715 St Charles Ave
Property Owner: Lawrence B Motley
Description: Convert theater to a resturant - the first floor conversion of 980 sf includes 477 sf of existing area into a commercial kitchen per plans. The remainder of the 1st floor including bar and restroom will remain. The 2nd and 3rd floor will not be part of this renovation and remain as existing.
Created By: etbrown
Status Information
Name Complete Date
Application Submitted Yes 7/1/2013
Application Review Yes 7/1/2013
Zoning Review Yes 8/6/2013
Plan Review Yes 8/6/2013
Permit Approved Yes 8/6/2013
Permit Issued Yes 8/6/2013
Inspections Finaled Yes 2/25/2014
Permit Finaled Yes 2/25/2014
Certificate of Occupancy Yes 2/25/2014
Fees
Type Amount Paid
Building $685.00 Yes
Building Plan Review $125.00 Yes
Reviews
Division Status Reviewer
Zoning Complete (8/6/2013)
Plan Review Complete (8/6/2013)
Review Comments
Division Status Comment
Plan Review Resolved Mechanical comments: 1. Please indicate the scope of the mechanical work. 2. If the cost of the mechanical work is less than $15,000.00, please provide estimates for actual labor and material cost from a licensed Mechanical Contractor (Heating, Ventilating & Air Conditioning), a licensed Gas Fitters, and a licensed Sheet Metal Contractor, all written under their business letterheads stating the correct permit number, the project address, license numbers, phone numbers with current dates. 3. If the cost of the mechanical work is more than $15,000.00, please submit mechanical plans and specifications prepared by a Louisiana Registered Mechanical Engineer with his fresh seal and fresh signed statement designating him as the professional of record per Section 106.1.1, IBC 2000 Edition (New Orleans Amendments). 4. Commercial kitchen hood ventilation system ducts and exhaust equipment shall meet all applicable requirements per Section 506 and its subsections; Kitchen hood construction/ installation shall meet all applicable requirements per Section 507 and its subsections; Commercial kitchen make up air shall meet requirements per Section 508 and Fire Suppression system shall meet requirements per Section 509. All of the above sections are per Chaper 5, IMC 2009. 5. Your mechanical (HVAC) plans as submitted do not bear LA registered professional mechanical engineer's seal designating him as the professional of record as required per code section 106.1.1, IBC 2006, New Orleans Amendments. Please submit duly stamped plans for our review. 6. Please comply with all of the above 5 items and submit detailed mechanical plans for our review.
Plan Review Resolved This project has been reviewed by Zachary Smith. Please reach him at 658-7114 if you have any questions. For email correspondence, please send to zrsmith@nola.gov.
Plan Review Resolved Please be aware that future submissions of Construction Documents may be made digitally with our online system or in person. You can access this website at www.nola.gov/onestop. Please combine all drawings into a single PDF file.
Plan Review Resolved Approval from the State Fire Marshal is required. Please contact the State Fire Marshal’s office at 8181 Independence Blvd., Baton Rouge, LA 70806, (225) 925-4920 / 800-256-5452 or 1450 Poydras St., Suite 1500, New Orleans, LA 70112, (504) 568-8506
Plan Review Resolved Plans shall be approved by Orleans Parish Sanitary Services, Dept. of Health and Hospitals at at 1450 Poydras St., Suite 1204, New Orleans, LA 70112 Please contact Sheryl Bradstreet at (504) 568-7970.
Plan Review Resolved Are all floors currently sprinklered?
Plan Review Resolved What is the occupancy of the 2nd and 3rd floors?
Plan Review Resolved What is the fire-resistance-rating of the ground floor ceiling separating the ground and 2nd floors?
Plan Review Resolved Plans show a rear alley to be used for egress. Please clarify ownership and ROW information to verify that the alley can be used by this property.
Plan Review Resolved If no use is planned for the 2nd and 3rd floors, access to these areas should be blocked so as not to allow travel to these areas.
Plan Review Resolved Electrical and Mechanical sheets appear to show work performed on the upstairs areas where the Scope of Work details only work on the ground floor. Please verify.
Plan Review Resolved Any modifications to the approved automatic sprinkler system must comply with Sec. 903 IBC 2009.
Plan Review Resolved Any modifications to the approved fire alarm system must comply with Sec. 907 IBC 2009.
Plan Review Resolved Commercial cooking equipment shall be installed in accordance with Section 904.11, IBC 2009. Please verify the NFPA standard reference of the automatic fire-extinguishing system to be installed.
Plan Review Resolved It appears that the stair opens into the kitchen area. Please note the Section 708 does not permit openings between floors.
Plan Review Resolved As per Section 1022, interior stairs shall be enclosed.
Plan Review Resolved Egress through intervening spaces (Dry Storage Room) shall be demarcated and maintain a 44” minimum aisle directly from retail area to exit without obstructions. Sec. 1014.2.2.4 IBC 2009 ed..
Plan Review Resolved Egress through kitchens is not permitted as per Section 1014. (please note that kitchen opens directly into storage room at rear)
Plan Review Resolved Verify compliance with door opening force section 1008.1.3 and door operations section 1008.1.9 of IBC 2009. (please detail all door hardware, especially that related to egress)
Plan Review Resolved Means of Egress Illumination must comply with Sec. 1006 IBC 2009 ed.
Plan Review Withdrawn Electrical review is PENDING.
Plan Review Resolved Electrical Review: Completed!
Inspections
Type Date Status
Final Building C/O 2/21/2014 9:30 AM Passed
General Inspection Unscheduled Unscheduled
Rough Framing 11/14/2013 10:00 AM Passed
Inspection Correction Items
Contractors
Name License
Montgomery & Associates Inc
Kirby Pecot
Details
Name Value
Is In Historic District Yes
Is In Vieux Carré No
Is In Neighborhood Conservation District Yes
Zoning CBD-7
Subdivision Lafayette Square
Historic District Name Lafayette Square
FEMA Zone B
Construction Value 125000
Existing Use Theater - Live Entertainment
Proposed Use Restaurant (50 People and Over)
Kitchen Added No
Parcel Tax Bill Numbers 103104107
Addresses 715 St Charles Ave [Le Chat Noir]
Square 22071005900.00000
Parcel ID Numbers 711-STCHARLESAV